Specifications
Measuring and control transmitter for panel installation in a Noryl® resin enclosure (front IP 54).
Sensors:
Connections for Swansensor Inducon1000 (inductive toroidal conductivity sensor with integrated Pt1000 temperature sensor) and for a digital sample flow meter.
Measuring range:
- 0 - 2000 mS/cm
- Conversion to concentration selectable for aqueous solutions of many chemicals.
User interface:
- Big backlit LC display for measuring value, sample temperature, sample flow and operating status
- Easy user menus in English, German, French and Spanish. Simple programming of all parameters by keypad
- Data logger for 1’500 data records stored at a selectable interval.
Connections:
- 2 signal outputs (0/4 - 20 mA) for measured values or continuous control
- 2 potential-free contacts as limit switches or as controllers, configuration normally open
- 1 potential-free alarm contact as summary alarm indication, default configuration normally open (option: normally closed)
- 1 input for potential-free contact for hold or remote-off function
- 1 serial interface RS232 for logger download
- Option: Profibus DP or Modbus RTU interface.
All in- and outputs protected against overvoltages.
Dimensions: 96 x 96 x 120 mm (DIN 43700)